METER TEST REPORT (60A,30A - 3PHASE)

ENERGY MANAGEMENT UNIT - SOUTHERN PROVINCE


General Information
Area : Ambalangoda Report No : EMSP/20180429/5
CSC : Gonapeenuwala Date of Test : 2018-04-21
Account Number : 4570104585 Tariff : -
Consumer Name : Kumara Jayantha walisinghe Mangala GPRS Cordinates : -
Address : No 459/B, Udugama Rd, Ambalangoda Contract Demand : 30 A 3-Phase
Meter Information
Make : Premier Meter Constant : 40 imp/kWh Accuracy Class : 1.0
Serial No : 094001537 MF (If any) : - Year of Manufacture : 2010
Meter Readings
Active Power : 8975801 kwh Voltage L1 : 233 V Current L1 : 7.5 A Avg Power Factor: 0.923
MD (Current) : 41.5 kVA Voltage L2 : 231 V Current L2 : 11 A
MD (History) : 45.6 kVA Voltage L3 : 234 V Current L3 : 12 A
Observation and Test Result
Meter Accuracy: OK Meter Wiring: OK Wiring Properly Done: Yes
Percentage Error: 0.456 to 1.586 Phase Sequence: Forword
Breaker
Breaker Type : MCB Capacity : 32 A Whether Supply Over Loaded : Yes
Enclosure
Available : Yes Properly Fixed : Yes Enclosure Condition : Good
Sealing
Terminal Old : CEB/DD4/4545454 CEB/DD4/4545457 Terminal New : CEB/DD4/4545478 CEB/DD4/4554589
Enclosure Old : CEB/DD4/4545442 CEB/DD4/447878 Enclosure New : CEB/DD4/78787845 CEB/DD4/5455544

 

Action Taken :

no action

 

Present Conditions :

Meter accuracy is Acceptable

 

Remarks :

In the above example, we needed four unique elements to get the job done. But that's four more elements than are appropriate semantically in our document. Ideal

 

Recomendation :

no recomendation

 


Copies to DGM (SP) Branch, Acct (Rev) Branch